Every water job starts with two questions. How many air movers go in, and how much dehumidification do they need behind them. Guess low and the job stalls. Guess high and the adjuster trims the equipment line. The IICRC publishes two short worksheets that answer both with arithmetic, and this article walks through them with the numbers filled in.
The standard behind them is ANSI/IICRC S500, the Standard for Professional Water Damage Restoration; the 2021 edition is current. The worksheets are the Airmover and Gallons Calculation Worksheet (Imperial revision 7.1.22) and the Initial Dehumidification Recommendation Factors and Formulas (Imperial revision 3.1.22). Both give initial placement. After the first day, the readings decide what changes.
Why the initial count matters
Drying is evaporation plus removal. Air movers move moisture off wet surfaces into the air; dehumidifiers take it out. If either side is short, the other is wasted. Too few air movers and the materials give up water slowly, so the job runs long. Too few dehumidifiers and the air loads up, evaporation slows and the readings flatten out. That flat line is a stall, and it usually shows on day two or three, the worst time to learn that the first-day count was wrong.
The count also matters on paper. Equipment is billed per unit per day, so the adjuster checks it first: how many units, in which rooms, for how many days, and on what basis. A file with the room dimensions, the class, the worksheet arithmetic and the daily readings answers all four before they are asked. An invoice on its own does not.
The four air mover steps
The air mover worksheet works room by room and gives each room a low range and a high range. Four steps, then a total.
- Step 1, one per room. Install one air mover in each affected room. This counts toward both ranges.
- Step 2, wet floor. Add one air mover for every 50 to 70 square feet of wet floor. This step covers the floor and the lower walls up to approximately 2 feet (24 inches), but the figure you use is the wet floor square footage only, excluding walls. Square feet divided by 70 is the low range; divided by 50 is the high range.
- Step 3, wall and ceiling above 2 feet. Add one air mover for every 100 to 150 square feet of wet wall and ceiling area above approximately 2 feet. Divided by 150 is the low range; divided by 100 is the high range.
- Step 4, insets and offsets. Add one air mover for each wall inset or offset greater than 18 inches. Closets and alcoves count. This goes into both ranges.
Add the four steps for the low total and again for the high total. Three notes on the worksheet govern the arithmetic. When a calculation comes out as a fraction, round up. In small rooms or areas under approximately 25 square feet, one air mover may be adequate. And where water has affected mainly the lower walls with limited flooring, a separate method applies, covered below, which is not combined with the square-foot method in the same room.
A worked example: one 20 by 15 room
Take a living room, 20 feet by 15 feet with an 8-foot ceiling, Class 2. The whole floor is wet, so the wet floor is 300 square feet. Water wicked up one wall above the 2-foot line over 120 square feet. One offset deeper than 18 inches steps back around a fireplace. Here is each step with both ranges.
| Step | Input | Low range | High range |
|---|---|---|---|
| 1. One per room | 1 room | 1 | 1 |
| 2. Wet floor | 300 sq ft | 300 / 70 = 4.29, rounds up to 5 | 300 / 50 = 6 |
| 3. Wall and ceiling above 2 ft | 120 sq ft | 120 / 150 = 0.8, rounds up to 1 | 120 / 100 = 1.2, rounds up to 2 |
| 4. Insets and offsets over 18 in | 1 offset | 1 | 1 |
| Total | 8 | 10 |
So the room needs 8 to 10 air movers on day one. Rounding does real work here: the floor alone gives 4.29 on the low side, and 4.29 air movers is 5. A room sitting at 7 would be under the worksheet on every reading of it.
How much water was there
The same worksheet includes the gallons calculation, which belongs in the file. Length times width times depth of water, all in feet, gives cubic feet; cubic feet times 7.48 gives gallons. One inch of standing water across the 300 square feet is 300 x 1/12 = 25 cubic feet, and 25 x 7.48 = 187 gallons before extraction.
The lower-wall alternative
Some rooms are wet at the base of the walls and almost nowhere else: water came through from the next room and migrated less than 2 feet into the floor. For that case the worksheet gives a different method: one air mover for each 14 affected linear feet of wall. A room with 40 linear feet of affected wall base gets 40 / 14 = 2.86, which rounds up to 3. This method stands on its own; it is not added to the square-foot steps in the same room.
The dehumidifier math
The second worksheet sizes dehumidification from the volume of the affected space and the class of the loss. The class reflects how much wet porous material the space holds and how hard it holds the water; the companion article on categories and classes covers assigning it. With the class in hand, read the factor from this chart.
| Dehumidifier type | Class 1 | Class 2 | Class 3 | Class 4 |
|---|---|---|---|---|
| Conventional refrigerant | 100 | 40 | 30 | N/A |
| Low grain refrigerant (LGR) | 100 | 50 | 40 | 40 |
| Desiccant (air changes per hour) | 1 | 2 | 3 | 3 |
The refrigerant formula: cubic footage divided by the chart factor gives total pints per day (PPD), and PPD divided by the dehumidifier's AHAM rating gives the number of dehumidifiers. Desiccants are rated by airflow, so their formula differs: cubic footage times the air changes per hour, divided by 60, gives total CFM, and that divided by the unit's CFM rating gives the number of units. The worksheet notes that the same CFM formula can size air filtration devices.
Same room, three ways
Back to the living room: 20 x 15 x 8 = 2,400 cubic feet, Class 2. Suppose the LGR on the truck is rated 70 pints AHAM, the conventional unit 50 pints AHAM and the desiccant 300 CFM. Those are illustrations; use the ratings printed on your own units.
| Type | Factor | Demand | Units |
|---|---|---|---|
| LGR | 50 | 2,400 / 50 = 48 PPD | 48 / 70 = 0.69, so one 70-pint unit |
| Conventional refrigerant | 40 | 2,400 / 40 = 60 PPD | 60 / 50 = 1.2, so two 50-pint units |
| Desiccant | 2 ACH | 2,400 x 2 / 60 = 80 CFM | 80 / 300 = 0.27, so one 300 CFM unit |
The conventional line shows why the factor matters. A conventional unit pulls less water from drier air, so the chart asks for more rated capacity in Class 2 (40 against 50 for an LGR) and gives no conventional factor for Class 4. You cannot place a fifth of a dehumidifier, so 1.2 units means two; note in the file that two 50-pint units carry 100 PPD against a 60 PPD demand.
Whole-job math across several rooms
Air movers are counted room by room, because the worksheet is written per room. Dehumidification is sized for the air the units share: rooms open to each other form one drying chamber and one volume, while a closed door or containment splits the space into chambers sized on their own. Here is the living room with a hallway and a bedroom open to it, all Class 2.
| Area | Dimensions (ft) | Cubic feet | Air movers, low | Air movers, high |
|---|---|---|---|---|
| Living room (above) | 20 x 15 x 8 | 2,400 | 8 | 10 |
| Hallway, 48 sq ft wet floor | 4 x 12 x 8 | 384 | 2 | 2 |
| Bedroom, 144 sq ft wet floor, one closet | 12 x 12 x 8 | 1,152 | 5 | 5 |
| Job total | 3,936 | 15 | 17 |
The hallway is 1 for the room plus 48 / 70 = 0.69 and 48 / 50 = 0.96, both rounding up to 1, so 2 on either range. The bedroom is 1 for the room, then 144 / 70 = 2.06 and 144 / 50 = 2.88, both rounding up to 3, plus 1 for the closet, so 5 on either range. The chamber holds 3,936 cubic feet. At the Class 2 LGR factor that is 3,936 / 50 = 78.72 PPD, and 78.72 / 70 = 1.12, so two 70-pint LGRs, one at each end of the chamber. Conventional units would face 3,936 / 40 = 98.4 PPD.
When one chamber holds rooms of different classes, a common approach is to size the shared dehumidification at the higher class and say so in the file. AIFSOP takes the volume from the LiDAR scan or the entered dimensions and suggests equipment type and quantity from that volume, the materials and the current readings, so this arithmetic is done before the technician leaves the room.
When to go above the low range
The worksheet gives a range on purpose. The low end is a floor, not a target. Reasons to place at the high end on day one, or above it, include:
- Dense or slow materials: hardwood, plaster, layered flooring, or framing that gives up water slowly.
- A lot of wet wall above 2 feet, or a wet ceiling, where surfaces sit at an awkward angle to the airflow.
- Water under cabinets, behind baseboards or inside wall cavities, where surface readings lag the cavity.
- Cool conditions, since evaporation slows as the surface cools.
- A Class 3 loss, where almost everything is wet and the evaporation load is at its highest.
Make a decision, not an average, and write down why. "Placed at high range: hardwood over subfloor, 120 sq ft wet wall" is one line, and it closes the question later.
Placement rules of thumb
The worksheets say how many. They do not say where. What follows is common field practice rather than standard text.
- Airflow goes across wet surfaces, not at them, so the saturated layer of air moves off the material and drier air replaces it.
- Set air movers at a 15 to 45 degree angle to the wall so the air runs along the wall and across the floor instead of bouncing back.
- Point every unit the same way around the room, usually clockwise, so the air circulates instead of fighting itself.
- Put the dehumidifier intake where the wettest air collects, usually toward the middle or the downstream side of the circulation, with its dry discharge feeding back into the pattern, and never aim an air mover straight into the intake.
- Leave unit numbers visible and photograph the setup from the doorway. That photo is the fastest proof of placement in the file.
What to log every day
The initial count is a prediction. The log is the evidence. A daily entry for each affected area holds three things.
- Readings. Temperature, relative humidity and GPP for the affected area, an unaffected reference and outside, plus the dehumidifier inlet and outlet, and moisture content for each monitored material and location against its drying goal. The psychrometrics article explains the numbers.
- Equipment counts. Air movers and dehumidifiers in each area, with unit identifiers and the days each has run.
- Changes. Every unit added, moved or removed, the reading that prompted it and the time. A removal with no reading beside it is the first thing a reviewer questions.
This is the second place software helps. AIFSOP keeps an equipment log per area next to the moisture log, so a unit moved from the bedroom to the hallway shows in both records, and an overdue reading raises an alert before the day is lost.
Documenting the initial calculation in the file
The calculation only protects you if it is in the file. The record should let someone who was not there reproduce every number.
- Room by room: dimensions, ceiling height, cubic feet, class, wet floor square feet, wet wall and ceiling square feet above 2 feet, and the count of insets and offsets over 18 inches.
- The four step results for each room, both totals, and the number placed with the reason for choosing it.
- For dehumidification: the chamber volume, the dehumidifier type, the factor, the PPD or CFM result, the rating of the units used and the number placed.
- The gallons estimate if there was standing water, and the extraction done first.
- Which worksheet revision the numbers came from, who ran the calculation and when.
Run the figures with the site's air mover calculator and dehumidifier calculator, which follow the same steps, then put the result in the job notes. The arithmetic takes five minutes on day one. Explaining its absence takes longer.