Dehumidifier calculator

The IICRC Initial Dehumidification Recommendation Factors and Formulas (Imperial revision 3.1.22): cubic feet divided by the class factor gives the pints per day a refrigerant or LGR unit must remove; cubic feet times air changes per hour, divided by 60, gives the CFM a desiccant must process.

The space

Measure the affected space, or the group of rooms that share air.

ft
ft
ft
pints/day

From the unit's specification sheet. Leave 0 to see the requirement only.

Cubic feet

2,400

20 × 15 × 8.0

Pints per day needed

48.0

2,400 ÷ 50

Low grain refrigerant (LGR) units

1

48.0 ÷ 70, rounded up

The factor chart

Imperial revision 3.1.22. Refrigerant factors are cubic feet per pint per day; desiccant factors are air changes per hour.

Dehumidifier typeClass 1Class 2Class 3Class 4
Conventional refrigerant1004030N/A
Low grain refrigerant (LGR)100504040
Desiccant (air changes per hour)1 ACH2 ACH3 ACH3 ACH

How the calculation works

Volume. Length × width × height of the affected space, in feet, is the cubic footage. Add rooms together when they share air.

Refrigerant and LGR. Cubic footage ÷ the chart factor = total pints per day (PPD). PPD ÷ a unit's AHAM rating = the number of units, rounded up. The factors are 100 / 40 / 30 for Classes 1 to 3 with a conventional refrigerant unit (no factor for Class 4) and 100 / 50 / 40 / 40 for Classes 1 to 4 with a low grain refrigerant unit.

Desiccant. Cubic footage × air changes per hour (1, 2, 3 and 3 ACH for Classes 1 to 4) ÷ 60 = total CFM. CFM ÷ a unit's CFM rating = the number of units. The worksheet notes the same formula sizes air filtration devices.

The result is the initial recommendation. ANSI/IICRC S500 expects the restorer to read conditions at least daily and adjust. The psychrometric calculator turns each day's temperature and humidity into grains per pound, and the air mover calculator covers the airflow side of the same worksheet set.

Sources

Questions this tool answers

How do you calculate dehumidifier pints per day for water damage?
Take the cubic footage of the affected space (length times width times height) and divide it by the factor for the class of water loss from the IICRC chart (Imperial revision 3.1.22): for a low grain refrigerant unit that is 100 for Class 1, 50 for Class 2 and 40 for Classes 3 and 4. The result is the pints per day of initial dehumidification. Divide by a unit's AHAM rating to get how many units.
What is the difference between an LGR and a conventional dehumidifier?
A low grain refrigerant (LGR) unit pre-cools incoming air so it keeps removing moisture at lower humidity, where a conventional refrigerant unit loses effectiveness. The chart reflects that: the conventional factors are 100, 40 and 30 for Classes 1 to 3 with no factor for Class 4, while LGR factors are 100, 50, 40 and 40.
How do you size a desiccant dehumidifier?
Multiply the cubic footage by the air changes per hour the chart gives for the class (1 for Class 1, 2 for Class 2, 3 for Classes 3 and 4) and divide by 60 to get the CFM of processed air needed. Divide by the unit's CFM rating for the number of units. The worksheet notes the same formula sizes air filtration devices.
Is the AHAM rating the same as the grain removal on a job?
No. The AHAM rating is a standard test condition (warm, humid air) that makes units comparable. On a job the unit removes less as the air dries, which is why daily inlet and outlet readings, not the nameplate, tell you whether the dehumidification is keeping up.
Does the calculator replace the standard?
No. It reproduces the IICRC's published initial factors and formulas so the first-day placement is defensible and documented. ANSI/IICRC S500 governs, and the readings over the following days decide every adjustment.

The app does this math on the job itself

AIFSOP suggests equipment from the scanned room volume, the class and the current readings, and logs every unit per area. 30-day free trial, no card.